S-2.1, r. 13 - Regulation respecting occupational health and safety

Full text
59. Enclosed dust collectors: Every enclosed collector for combustible dust or any other suspended matter presenting a fire or explosion hazard must
(1)  be designed, manufactured and maintained according to the rules of the trade; and
(2)  be placed and installed
(a)  outside a building if provided with explosion vents in compliance with NFPA Standard 68-1998 Guide for Venting of Deflagrations; vents already installed on collectors on 4 January 2007 must also comply with that standard or with the standard applicable at the time of installation of the vents and be in good order;
(b)  inside a building in either of the following cases:
i.  if adjacent to an outside wall or ceiling towards which the explosion vents are channelled by explosion proof ducts and if they comply with NFPA Standard 68-1998 Guide for Venting of Deflagrations; vents already installed on the collectors on 4 January 2007 must also comply with that standard or with the standard applicable at the time of the installation of the vents and be in good order; or
ii.  if equipped with an automatic explosion prevention system in compliance with NFPA Standard 69-2002 Explosion Prevention Systems; the automatic prevention systems installed on the collectors on 4 January 2007 must also comply with that standard or with the standard applicable at the time of the installation of the systems and be in good order.
O.C. 885-2001, s. 59; O.C. 1120-2006, s. 1.